РУС   УКР   ENG
Gas modular burners of type GGS-B

 

Gas modular burners of type GGS-B

The burners are intended for burning natural gas in steam and hot-water boilers as well as in other heat appliances. The burners are delivered with: set of pickups and indicating instruments required for control of the technological process.

 

 

Technical Characteristics:

№ os. Parameters description

GGS-B-0,85

GGS-B-1,4

GGS-B-2,2

GGS-B-3,5

1. Rated heat power of the burner,MW

0,85

1,4

2,2

3,5

2. Consumption of natural gas:
— under rated thermal power, nm3/h
— under minimal thermal power, nm3/h

90

22

139

47

230

55

360

90

3. Connection pressure of gas, kPa, not over
— at middle value, kPa
— at low value 

 

40

4,5

4. Rated pressure of gas before the burner, kPa, not over:
— middle
— low

20

1,5

27

5. Rated pressure of air before the burner, kPa, not over

1,1

1,2

1,3

1,5

6. Coefficient of working regulation of the burner, not lower than

4

7. Rated length of the flame, not over, m

1,5

1,9

2,4

2,8

8. Rated pressure in the burning chamber, RPa, not over

 

600

9. Specific consumed electric power, kW/MW, not over kW/Mw

1,4

2,5

4,4

5,8

10. Mass, kg, not over

130

170

230

260

11. Overall dimensions, mm, not over:
— length, L
— height (with gas unit), Н
— width, В

 

970
1050
900

 

970
1050
900

 

1000
950
850

 

1000
1100
900

12. Distance between axes of fastening holes, mm

255

275

365

465

13. Diameter of fastening holes, mm

18

14. Power supply voltage, V

380 / 220

15. Ignition system

spark from high voltage transformer



 



 
 
 
 
Creation of a site —