РУС   УКР   ENG
Burners \ Burners with variable values of extra air ПИВ
Two-passage gas burners:

 

Burners with variable values of extra air ПИВ

They are intended for use in the heating systems of heated, thermal furnaces and driers in the machine building and metal processing branches of industry. Climatic version 0 of category 4, GOST 15150-69. The burner includes a pilot-protective device (УПЗ)/PPD/ with thermal power of 5 kW. Depending upon the variant of the PPD burners may be delivered: 1-with the control electrode, 2-with the photo sensor holder. Depending upon the variant of the perforated pipe for discharge of burning wastes the burners may be delivered:
1 — pipe with holes uniformly distributed along the circumference and length;
2 — pipe with non-uniformed perforation: holes are distributed along the length within an angle of 150°.


Technical Characteristics

Parameter description Burner standard dimensions
ПИВ 60 ПИВ 120 ПИВ 450 ПИВ 700
1. Rated thermal power, kW 70,0 140,0 540,0 815,0
2. Rated gas consumption, m3/h 7,0 14,0 55,0 80,0
3. Rated air consumption, m3/h 140,0 280,0 1100,0 1600,0
4. Rated gas pressure before the burner, kPa 3,0 4,6 4,5 3,6
5. Rated air pressure for burning before the burner, kPa 4,4 3,6 4,15 3,15
Rated consumption for PPD, m3/h:
— of gas 0,5 0,5 0,5 0,5
— of air 5,0 5,0 5,0 5,0
7. Rated gas pressure before the PPD, kPa, not over 3,7 3,7 3,7 3,7
8. Rated air pressure before the PPD, kPa 3,8 3,8 3,8 3,8
9. Minimal coefficient of extra air under rated thermal power 2,0 2,0 2,0 2,0
10. Coefficient of burner operation regulation), not lower than 8,0 8,0 8,0 8,0
11. Rated pressure (rarefaction) in the chamber of burning of the heat unit, Pa, not over 20 20 20 20
12. Mass of the burner, kg, not over 49 78 235 212
L 1225 1525 2180 2500
H 282 325 580 633
L1 238 235 350 455
L2 285 380 660 590
L3 555 800 1130 1330
H1 170 190 350 400
H2 120 150 220 260
D 160 194 325 362
D1 200 245 420 430
D2 130 170 280 305
D3 121 146 219 245
d1 76 108 218 245
d2 14 18 22 18
d3 14 14 22 22
K″ 1/2 3/4 1 1/2  2
α0  at the customer's option
n2 4 4 8 8
n3 6 8 8 12






 
 
 
 
Creation of a site —