Gas-oil burners with regulated flame ГМР
These burners are intended for use in the heating systems of high-temperature industrial furnaces for various applications in the modes of «long» and «short» flames and for low-temperature furnaces only in the mode of «short» flame in which it is possible to use gas, oil or any other liquid fuel with their separate or combined combustion. The regulation of the flame parameters is achieved due to redistribution of the fan air between two air ducts, direct duct and duct with a swirler. The burners are not fit for repair. Burners ГМР are manufactured in the climatic version of mounting 3 according to GOST 15150-69. Burners ГМР are manufactured in seven standard sizes according to the thermal power and depending on the body construction: 1 — with normal burner body for all rated consumptions of gas; 2 — with elongated burner body (only for rated consumptions of gas 50, 100, 150 nm3/h).
Technical Characteristics
| Parameter description |
Parameter value |
| ГМР-50 |
ГМР-100 |
ГМР-150 |
ГМР-300 |
ГМР-500 |
ГМР-700 |
ГМР-1000 |
| 1. Rated thermal power of the burner, kW |
500 |
1000 |
1500 |
3000 |
5000 |
7000 |
10000 |
| 2. Nozzle efficiency, kg/s |
0,012 |
0,024 |
0,038 |
0,074 |
0,122 |
0,172 |
0,245 |
| 3. Coefficient of burner operation regulation for power, not lower than |
|
| — when working with gas |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
| — when working with oil |
4 |
4 |
4 |
4 |
4 |
4 |
4 |
| 4. Rated pressure before the burner, kPa, not over: |
|
| — air |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
| — gas |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
| — oil |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
| — spraying air (steam) |
300 |
300 |
300 |
300 |
300 |
300 |
300 |
| 5. Rated pressure (rarefaction) in the combustion chamber of he heat unit, Pa |
0±100 |
0±100 |
0±100 |
0±100 |
0±100 |
0±100 |
0±100 |
| 6. Range of pressures (rarefactions) in the combustion chamber of the heat unit in which the burner may be used, kPA |
±0,2 |
±0,2 |
±0,2 |
±0,2 |
±0,2 |
±0,2 |
±0,2 |
| 7. Specific consumption of spraying air(steam), kg/kg, not over |
1,0 |
1,0 |
1,0 |
1,0 |
1,0 |
1,0 |
1,0 |
| 8. Average service life of the burner until the overhaul with the exception for automatic devices, ceramic tunnel and wearing elements, h, not lower than |
2700 |
2700 |
2700 |
2700 |
2700 |
2700 |
2700 | |